Section 47

No licence shall be granted for the storage of a larger quantity of non-dangerous petroleum than two hundred gallons or a larger quantity of dangerous petroleum than fifty gallons save in accordance with the following quantities and conditions –

(a)

in packages –

(i)

in a fireproof compartment inside another building – total not exceeding 200 gallons;

For Reference Only

Subsidiary Legislation 5 of 16

Petroleum Rules 1960

(ii)

in a fireproof store not less than ten feet from any house or building – total not exceeding 200 gallons;

(iii)

in a fireproof store not less than twenty-five feet from any house or building - unlimited quantity;

(iv)

in a shed or outhouse not less than thirty feet from any house or building which is of fireproof construction

– total not exceeding 200 gallons;

(b)

in steel drums not exceeding fifty gallons capacity in the open air – not less than fifty feet from the boundary of any house or building – unlimited quantity;

(c)

in underground tanks –

(i)

under another building with top of tank below floor level – total not exceeding 1,000 gallons;

(ii)

under another building with top of tank below all floor levels within twenty feet – total not exceeding 5,000

gallons;

(iii)

in open air not less than ten feet from the boundary of any house or building with top of tank below all floor levels within twenty-five feet – unlimited quantity;

(d)

in aboveground tanks – at a distance from the boundary of any building used or intended to be used for human habitation or occupation not exceeding –

(1)

ten feet – total not exceeding 10,000 gallons;

(2)

fifteen feet – total not exceeding 10,000 to 24,000 gallons;

(3)

twenty feet – total not exceeding 24,000 to 30,000 gallons;

(4)

twenty-five feet – unlimited quantity.

Underground tanks.